Intellect-69 (INT69)

Ratemeter & Totalizer from Analog Inputs

The Intellect-69 is an integrating totalizer & ratemeter which accepts analog signal inputs. The unit can be field programmed to accept 4-20mA, 0-20mA, 0-5V, 0-10V or 1- 5V signals. An optional Square Law input is available for inputs that require square root extraction. A 4-20mA output option is available to control strip recorders or other peripherals.

Features

  • High/Low Scaling From Front Panel
  • 2 Set Points Assignable To Rate or Total
  • Relay Outputs
  • Display Rate (pressure, level, watts, etc.),Peak & Valley and Integrated Total
  • 0-5V, 0-10V, 1-5V, 4-20mA or 0-20mA AnalogInput
  • NEMA 4X/IP 65 Front Panel
  • +24V Output For Peripherals
  • RS422/232 Serial Communications
  • 4-20mA Output
  • Square Root Extraction

Literature





Training Aids





(Coming Soon)

FAQ

There are several reasons this could be happening. Please check the following:

Analog or Voltage loop broken. Check connections to make sure signal is getting to the unit.
Check that the set high and set low are NOT set to zero.
Input resistor burnt up. Check with multimeter across terminal 3 and 4, it should read 100 ohms.

There are several reasons this could be happening. Please check the following:

Make sure the input selection is selected for the correct input (4-20mA, 0-20mA, 0 –10vdc, 1-5vdc)
Under setup in the program make sure the set high and set low are set correctly
Check that the nor (normalization) is not set too high. If set at more then 50 the display will update very slowly.

 

There are several reasons this could be happening. Please check the following:

Make sure the presets are not set at zero
Under setup in the program make sure the totalizer is not set for HOURS and the tFACT for 1000.

There are several reasons this could be happening. Please check the following:

The “set low” is set at a value other then zero.
The input has a value higher then 4mA on it. ¾
Make sure the input selection is selected for the correct input (4-20mA, 0-20mA, 0 –10vdc, 1-5vdc)

When the Relays are assigned to total and there is a duration set other than zero, the totallizer will count up to the preset value then the relay will close for the set duration of time and the totalizer will aut-reset to zero.
If this is not the desired operation enter the programming menu and under relays in the program change the “dur” (duration) to .00 or change the relays to follow the rate display.

 

Please try the following:

Make sure that the analog out option was ordered (check the model number to see if this option is specified)
The Analog Output is a sinking output and must be looped to a power source that is not common with the INT69. Preferably out of terminal 7 through meter and back to terminal 2.

 

The user can view the Rate ,Total , Peak and Vally of flow by pressing the view button on the front of the unit. The Peak is the highest value the display has read and the vally is the lowest value.

The Intellect-69 has EEPROM memory and is capable of storing program and count data for a minimum of 10 years. This is also referred to as non-volatile memory

The DC output isavalable when the unit is powered with AC Voltage. The D.C. output is rated at 50ma maximum current draw.

Yes, you can set the Set Hi at a low value and the Set Lo at a High value.
This is also true for the Analog out put as well.

Below you will find typical wiring diagrams to help you connect a flowmeter:

Number of items found

Accessories


LCN4X Low Cost NEMA4X

MS821 NEMA4X Enclosure

MS828 NEMA4X Enclosure
with Instrument Panel

XHV Explosion Proof
Housing for  Hazardous Areas

P20 Thermal Printer

P220 Impact Printer

IEPS-3000 Intelligent
EthernetMulti Port Server

IEPS-1000 Intelligent
Ethernet Single Port Server

CA285RS-422/RS-485
to RS-232 Interface Converter
Malcare WordPress Security